The Air Handling Unit (AHU) Design & Cleanroom Sizer Calculator provides a rigorous thermodynamic and aerodynamic design platform for pharmaceutical cleanroom HVAC systems. It sizes supply airflows, chilled water cooling coil capacities (kW / Tons of Refrigeration), sensible and latent heat loads, reheat duty, 3-stage cleanroom filtration pressure drop, and total static fan motor horsepower (HP).
The design engine complies with ISO 14644-1/4, EU GMP Annex 1 (2022 Revision), ISPE Good Practice Guide: Heating, Ventilation, and Air Conditioning (HVAC), and ASHRAE Fundamentals Handbook.
Saturation pressure of water vapor pws(T) is computed using the ASHRAE / Sonntag formulation (accurate between −40∘C and +60∘C):
pws(T)=611.213⋅exp(241.2+T17.5043⋅T)[Pa]
When outdoor wet bulb temperature Twb is given, water vapor partial pressure pv is determined using the Carrier / Stoecker psychrometric wet-bulb formulation:
pv=pws(Twb)−1555.56−0.722⋅Twb(Patm−pws(Twb))(Tdb−Twb)[Pa]
W=0.62198⋅Patm−pvpv[kg water / kg dry air]
h=1.006⋅Tdb+W⋅(2501+1.86⋅Tdb)[kJ / kg dry air]
- Moist Air Density (ρ):
ρ=Rda(Tdb+273.15)(1+1.6078W)Patm(1+W)[kg/m3]
For each cleanroom zone i, supply airflow Vsupply,i is determined by the maximum of:
- Air Changes per Hour (ACPH) Criterion:
VACH,i=3600Volumei×ACHi[m3/s]
- Thermal Sensible Heat Removal Criterion:
Vthermal,i=ρ⋅cp⋅(Troom,i−Tsupply)Qsensible,total,i[m3/s]
- Minimum Ventilation / Pressurization Leakage:
VOA,i=max(1000Occupantsi⋅OAperson,Vexhaust,i+Vleakage,i)
Vsupply,total=i∑max(VACH,i,Vthermal,i,VOA,i)
Tmixed=VsupplyVOATOA+VRATRA,Wmixed=VsupplyVOAWOA+VRAWRA
Using Apparatus Dew Point (ADP) and Coil Bypass Factor (BF=0.08 for deep 8-row cleanroom coils):
- Total Cooling Capacity (Qc):
Qcooling=m˙air⋅(hmixed−hoff−coil)[kW]
Tonnage=3.51685Qcooling[TR]
- Sensible Cooling Capacity:
Qcs=m˙air⋅cp⋅(Tmixed−Toff−coil)[kW]
Qcl=Qcooling−Qcs[kW]
- Chilled Water Flow Rate (6.5∘C→12.0∘C):
V˙CHW=4.186⋅(TCHW,return−TCHW,supply)Qcooling[L/s]
- Condensate Drainage Rate:
m˙condensate=m˙air⋅(Wmixed−Woff−coil)⋅3600[L/h]
In pharmaceutical HVAC, air off the cooling coil (10∘C−12∘C) is cold and saturated. It is reheated to design supply air temperature (15∘C−17∘C) to prevent room overcooling:
Qreheat=m˙air⋅cp⋅(Tsupply−Toff−coil)[kW]
- Pre-Filter (G4 / MERV 8): 150 Pa
- Fine Secondary Filter (F9 / MERV 15): 250 Pa
- Terminal HEPA Filter (H14 / 99.995% EN 1822): 450 Pa
- Internal Coils & Dampers: 130 Pa+60 Pa+40 Pa=230 Pa
- External Static Pressure (ESP - Ducts & Silencer): 280 Pa+50 Pa=330 Pa
TSP=(InternalΔP+ESP)⋅(1+Safety Margin)
Fan Shaft Power Pshaft=1000⋅ηfanVsupply⋅TSP[kW]
Motor Required Pmotor=ηmotorPshaft[kW]
Motor Horsepower HP=Pmotor⋅1.34102[HP]
ΔTfan=ρ⋅cp⋅1000⋅ηfanTSP≈+0.8∘C to +1.4∘C
| Grade / Class | Airflow Pattern | Target ACPH | Max Particles ≥0.5μm (Rest) | Max Particles ≥0.5μm (Action) | Differential Pressure |
| Grade A (ISO 5) | Unidirectional (0.45 m/s) | 60+ ACPH | 3,520 / m³ | 3,520 / m³ | +15 Pa to +20 Pa |
| Grade B (ISO 5) | Turbulent / Mixed | 40 – 60 ACPH | 3,520 / m³ | 352,000 / m³ | +15 Pa cascade |
| Grade C (ISO 7) | Turbulent | 20 – 30 ACPH | 352,000 / m³ | 3,520,000 / m³ | +15 Pa cascade |
| Grade D (ISO 8) | Turbulent | 10 – 20 ACPH | 3,520,000 / m³ | Not Defined | +10 Pa cascade |
- ASHRAE Handbook — Fundamentals (SI Edition): Chapter 1 Psychrometrics and Chapter 17 Clean Spaces.
- ISO 14644-1:2015: Cleanrooms and associated controlled environments — Part 1: Classification of air cleanliness.
- ISO 14644-4:2001: Cleanrooms — Part 4: Design, construction and start-up.
- EU GMP Annex 1 (2022): Manufacture of Sterile Medicinal Products.
- ISPE Good Practice Guide: Heating, Ventilation, and Air Conditioning (HVAC).
- EN 1822 / ISO 29463: High efficiency air filters (EPA, HEPA and ULPA).